Sesija: PRODUŽAVANJE RADNOG VEKA POSTOJEĆIH ELEKTRANA I SISTEMA - MOGUĆNOSTI I IZAZOVI
Strategija i instrumenti za investiranje u nova postrojenja; dijagnostika stanja opreme i preostali radni vek, dijagnostika procesa, planiranje, realizacija i analiza revitalizacionih zahvata, unapređenja na mašinskoj i elektroopremi.
Radovi odabrani za sesiju Konferencije pod nazivom: PRODUŽAVANJE RADNOG VEKA POSTOJEĆIH ELEKTRANA I SISTEMA - MOGUĆNOSTI I IZAZOVI
nazad na Sesije
Predrag Blagojevic, Slobodan Spasojevic (EPS AD, Ogranak Drinsko Limske hidroelektrane)
Abstrakt
Tema ovog rada je sanacija i adaptacija agregata R2 RHE u elektrani Bajina Bašta, sa ciljem optimizacije njegovog rada i povećanja energetske efikasnosti. Agregati RHE su ključni element u sistemu proizvodnje električne energije, te je neophodno redovno održavanje i prilagođavanje tehnološkim novinama kako bi se osigurala njegova pouzdanost i dugoročan rad.
Radovan Đukanović (EPCG, HE „Perućica“, Nikšić)
Abstrakt
HE „Perućica“ je najstarija velika hidroelektrana u Crnoj Gori puštena u rad 1960.
godine. Nalazi se na teritoriji opštine Nikšić, u sjevernom dijelu Bjelopavlićke ravnice.
Koristi vode sliva rijeke Gornja Zeta, čije slivno područje iznosi 850 km 2 , uz njihovo
veoma dobro iskorišćenje imajući u vidu bruto pad od 550 m. Njena instalisana snaga je
307 MW, a moguća godišnja proizvodnja 1300 GWh električne energije. U novije
vrijeme usled energetske tranzicije i sve većeg broja solarnih i vjetroelektrana
akumulacione hidroelektrane, kao što je Perućica, sve više dobijaju na značaju zbog
mogućnosti pružanja usluga isporuke balansne energije i sekundarne i tercijarne
regulacije.
Biće prezentovani opšti i tehnički podaci o HE „Perućica“, proizvodni rezultati kao i njen
značaj u elektroenergetskom sistemu Crne Gore. Posebna pažnja je posvećena
projektima za unapređenje kapaciteta i efikasnosti rada, a odnose se na realizaciji
druge faze rekonstrukcije i modernizacije koja obuhvata rekonstrukciju preostala tri
agregata, opremu zatvaračnica dovodnog sistema, unapređenje sistema upravljanja,
rekonstrukciju svih generatorskih polja u RP 110 kV, kao i ugradnju najsavremenije
opreme za hidrološka i hidraulična mjerenja za projekat optimizacije korišćenja voda
nikšićkog polja, na ugradnju još jednog agregata snage 58,5 MW, i na projekat
prevođenja vode rijeke Zete u akumulaciju Krupac i spajanje jezera Krupac i Slano, a
sve sa ciljem produženja životnog vijeka, povećanja snage i proizvodnje, obezbjeđenja
visoke pogonske spremnosti i što boljeg iskorišćenja raspoloživih voda naročito u
periodima velikih padavina kada imamo veći dotok nego što je potrebno za maksimalnu
snagu Perućice.
Sva tri projekta su u toku i njihov završetak se očekuje u narednom trogodišnjem
periodu čime ćemo dobiti kompletno modernizovanu elektranu sa značajnim navedenim
benefitima.
HPP Perućica is the oldest large hydroelectric power plant in Montenegro,
commissioned in 1960. It is located in the municipality of Nikšić, in the northern part of
the Bjelopavlić plain. It uses the water of the Gornja Zeta river basin, which has a
catchment area of 850 km², utilizing them very efficiently considering the gross head of
550 m. Its installed capacity is 307 MW, and the possible annual production is 1300
GWh of electricity. Recently, due to the energy transition and the increasing number of
solar and wind power plants, storage hydroelectric plants like Perućica are becoming
increasingly important because of their ability to provide balancing energy services and
secondary and tertiary regulation.
General and technical data about the "Perućica" Hydroelectric plant, its production
results, as well as its significance in the electric power system of Montenegro, will be
presented. Special attention is given to projects aimed at improving capacity and
operational efficiency, relating to the implementation of the second phase of
reconstruction and modernization, which includes the reconstruction of the remaining
three units, equipment for the inlet system shut-off valves, upgrading the control system,
reconstruction of all generator fields in the 110 kV switchyard, as well as the installation
of the most advanced equipment for hydrological and hydraulic measurements for the
project optimizing the use of water in the Nikšić field, the installation of an additional
58.5 MW unit, and the project for diverting water from the Zeta River into the Krupac
reservoir and connecting the Krupac and Slano lakes. All of this aims to extend the
plant's operational life, increase its capacity and production, ensure high operational
readiness, and make the best use of available water resources, especially during
periods of heavy rainfall when inflow exceeds what is needed for maximum power of
Perućica.
All three projects are underway, and their completion is expected within the next three-
year period, which will result in a fully modernized power plant with significant
mentioned benefits.
Aleksandar Petkovic (Lecturer, Academy of Applied Studies “Polytechnic”, Belgrade)
Jovan Ilic (PhD student, University of Belgrade, Faculty of Mechanical Engineering, Belgrade)
Abstrakt
Cooling water systems are one of the most important auxiliary systems at hydropower plants and are applied to serve the main generating equipment (i.e. generating units and step-up transformers). Their function is to assure prerequisites for unrestricted long-term operation of the main generating equipment under all exploitation circumstances (i.e. number of generating units in operation, their operating power, during all seasons of the year). The paper discusses conceptual solutions of these systems (open- and closed- loop; joint, group and individual sets for preparation of cooling water; water delivery by pumping from tailwater, intaking from turbine spiral casings followed by ejector jet pumping or by pressure reducing), characteristics of the main items of equipment, characteristics of cooling water consumers and design criteria for selection of technical solutions therein. As well, case study of refurbishment (reconstruction and modernization) of cooling water system of generating units of HPP Vrla 1 (of 4 x 14 MW installed output) is briefly presented.
Radomir Radiša, Pavle Stepanić, Ivana Vasović, Aleksandar Stepanović, Srećko Manasijević (Lola Institute Ltd, Kneza Višeslava 70a, Belgrade)
Abstrakt
Maintenance of components of the hydroelectric power plant system is essential for the safe and secure operation of the entire plant. A key role is played by analyzing the remaining service life of machine parts that are still in operation and must be replaced before final breakage, which would cause the system to fail. A detailed and comprehensive analysis of the system elements can prevent high costs or intangible losses that may result from failures or breakages of machine parts in the hydroelectric power plant. To efficiently replace worn and damaged parts and produce new ones, the maintenance section of HPP Djerdap 1 uses the LITOSTROJ PD 2000-6000 SM lathe. This lathe can process large machine parts, such as turbine blade sleeves. The subject of this paper is the analysis and reconstruction of a lathe that causes inadequate bearing of the turbine blade due to inaccurate machining. The existing solution did not meet the quality and tolerance requirements for the treated surfaces because it failed to achieve the required geometry and precision in turbine blade processing. By analyzing the existing solution and accounting for possible reconstruction limitations, a solution with existing radial bearings and their stiffening is presented. Through the research, a newly designed bearing with bearings that carry both types of loads (radial and axial) was proposed. The original solution with two bearings that were not sufficiently stiffened required refinements to the housing and the rings that define the bearings' positions. The research results are presented in the paper, and their validity has been confirmed through experimentation, component installation, and the reconstruction of the machine, which was later improved to achieve the required operating parameters.
Ljiljana Velimirović, M.Sc.Mech.Eng. (Project Manager I, Investment Department, JSC EPS, Rukovodilac projekta I, Sektor za investicije, EPS AD)
Dr Andrej Stanimirović, B.Sc.Mech.Eng. (Project Manager II, Development Department, JSC EPS , Rukovodilac projekta II, Sektor za razvoj, EPS AD)
Abstrakt
The paper presents the current state after implementation of one of the key investment projects of JSC EPS, "Construction of flue gas desulfurization plant of thermal power plant "Nikola Tesla" A3-A6" in accordance with the provisions of the Interstate Agreement with the Government of Japan. The project was financed by a loan from Japan International Cooperation Agency.
Wet-limestone desulfurization technology was applied. In the process, limestone (calcium carbonate) is consumed and gypsum (calcium sulfate dihydrate) is obtained as a by-product. Flue gases, after filtering particulate matter in electrostatic precipitator, are via flue ducts introduced to the absorber, which in the technological sense is the most important part of the FGD plant, where sulfur oxides (SOx) are absorbed by intensive mixing with limestone suspension. The limestone suspension is injected using nozzles placed in 4 levels inside the absorber.
In the reaction of limestone, water, oxygen and SO2 from flue gases, gypsum (CaSO4x2H2O) crystals are obtained in the reaction part of the absorber, which is then taken from the absorber in the form of a 15% gypsum suspension to the drying and storage process, or to thickening and depositing. A significant part of the particles from the flue gas remaining after electrostatic precipitator is retained in the absorber. Purified flue gas is discharged from the absorber through a 140 m high wet chimney into the atmosphere.
The absorber part of FGD plant consists of two tower absorbers with counter-current flue gas flows, one for units A3 and A4, and one for units A5 and A6, each with a capacity of 3,424.26 Nm3/h of dry flue gas. The auxiliary part of the plant is related to reception and processing of limestone as well as gypsum drying. The produced dry gypsum of EURO quality is intended for commercial sale and is used in the construction industry.
Input parameters:
- Input power per absorber 700 MW
- Flue gas flow at absorber inlet (wet) 3.424.260 Nm3/h
- Flue gas temperature 175°C
- Max. SO2 content (6% O2, dry) 6000 mg/Nm3
- PM content 50 mg/Nm3
Requested output parameters:
- SO2 content (6% O2, dry) < 130 mg/Nm3
- PM content < 20 mg/Nm3
- Mist emission < 100 mg/Nm3
Apstrakt: Rad prikazuje aktuelno stanje nakon realizacije jednog od ključnih investicionih projekata EPS AD, „Izgradnja postrojenja za odsumporavanje dimnih gasova termoelektrane „Nikola Tesla A3-A6““ u skladu sa odredbama međudržavnog Sporazuma sa Japanom. Projekat je finansiran iz zajma potpisanog sa Japan International Cooperation Agency.
Primenjena je tehnologija odsumporavanja vlažno-krečnjačkim postupkom. U procesu se troši krečnjak (kalcijum karbonat) i dobija se kao nusproizvod gips (kalcijum sulfat dihidrat). Dimni gasovi se nakon filtriranja praškastih materija u elektro-filtru preko dimovodnih kanala vode u apsorber, koji u tehnološkom smislu predstavlja najvažniji deo gde se vrši apsorpcija sumpornih oksida (SOx) intenzivnim mešanjem sa krečnjačkom suspenzijom. Ubrizgavanje krečnjačke suspenzije se vrši pomoću mlaznica koje su unutar absorbera postavljene u 4 nivoa.
U reakciji krečnjaka, vode, kiseonika i SO2 iz dimnih gasova, u reakcionom delu apsorbera dobijaju se kristali gipsa (CaSO4x2H2O) koji se iz apsorbera u vidu 15% gipsane suspenzije odvodi na proces sušenja i skladištenja ili na zgušnjavanje i deponovanje. Značajan deo čestica iz dimnog gasa, preostalih nakon elektro-filtera zadržava se u apsorberu. Prečišćeni dimni gas, odvodi se iz apsorbera, preko vlažnog dimnjaka visine 140m u atmosferu.
Apsorberski deo postrojenja se sastoji od dva toranjska absorbera sa suprotosmernim tokovima dimnog gasa, jedan za blokove A3 i A4, jedan za blokove A5 i A6 kapaciteta 3.424.26 Nm3/h suvog dimnog gasa. Drugi deo postrojenja se odnosi na prijem i obradu krečnjaka kao i sušenje gipsa. Proizvedeni suvi gips EURO kvaliteta je namenjen za komercijalnu prodaju i ima primenu u građevinskoj industriji.
Ulazni parametri:
- Snaga po absorberu 700 MW
- Protok dimnog gasa na ulazu u absorber (vlažan) 3.424.260 Nm3/h
- Temperatura dimnog gasa 175°C
- Maks. sadržaj SO2 (6% O2, suv) 6000 mg/Nm3
- Sadržaj praškastih materija 50 mg/Nm3
Zahtevani izlazni parametri:
- Sadržaj SO2 (6% O2, suv) < 200 mg/Nm3
- Sadržaj praškastih materija < 20 mg/Nm3
- Emisija kapljica < 100 mg/Nm3
Dr Andrej Stanimirović, B.Sc.Mech.Eng. (Project Manager II, Development Department, JSC EPS , Rukovodilac projekta II, Sektor za razvoj, EPS AD)
Ljiljana Velimirović, M.Sc.Mech.Eng. (Project Manager I, Investment Department, JSC EPS , Rukovodilac projekta I, Sektor za investicije, EPS AD)
Abstrakt
The paper describes the current state of implementation of one of the key investment projects of JSC EPS - Construction of flue gas desulfurisation plant of the thermal power plant "Nikola Tesla" B.
Wet-limestone desulfurisation technology was applied. In the process, limestone (calcium carbonate) is consumed and gypsum (calcium sulfate dihydrate) is obtained. Flue gas enters the flue gas desulfurisation plant after filtering particulate matter in an electrostatic precipitator. Flue gas is carried through flue ducts to the absorber, where sulfur oxides (SOx) are absorbed by intensive mixing with limestone suspension. A significant part of the particles from the flue gas remaining after the electrostatic precipitator is retained in the absorber. Purified flue gas is released into the atmosphere through a wet stack. In the reaction tank at the bottom of the absorber, gypsum crystals are obtained as a product of the chemical reaction of limestone and sulfur oxides from flue gas.
The plant consists of two tower absorbers with counter-current flows of flue gas and limestone suspension, one for each unit, with a capacity of 6,554,469 Nm3/h of flue gas. The limestone suspension is injected using sprinklers that are placed in several levels inside the absorber.
A plant for delivery and grinding of limestone, i.e. preparation of limestone suspension, as well as a plant for gypsum drying, is also being built. The produced gypsum can be deposited in a landfill, in the form of a thick slurry with ash and slag, or in a gypsum storage for sale.
Input parameters:
- Input power per absorber 650 MW
- Flue gas flow at absorber inlet (wet) 6.554.469 Nm3/h
- Flue gas temperature 180°C
- Max. SO2 content (6% O2, dry) 4984 mg/Nm3
- PM content 50 mg/Nm3
Requested output parameters:
- SO2 content (6% O2, dry) < 130 mg/Nm3
- PM content < 20 mg/Nm3
- Mist emission < 100 mg/Nm3
Apstrakt: Rad prikazuje aktuelno stanje realizacije jednog od ključnih investicionih projekata EPS AD - Izgradnja postrojenja za odsumporavanje dimnih gasova termoelektrane „Nikola Tesla“ B.
Primenjena je tehnologija odsumporavanja vlažno-krečnjačkim postupkom. U procesu se troši krečnjak (kalcijum karbonat) i dobija gips (kalcijum sulfat dihidrat). U postrojenje za odsumporavanje dimnih gasova dimni gas ulazi nakon filtriranja čestičnih materija u elektro-filtru. Dimni gas se dimnim kanalima sprovodi do absorbera, gde se vrši apsorpcija sumpornih oksida (SOx) intenzivnim mešanjem sa krečnjačkom suspenzijom. Značajan deo čestica iz dimnog gasa, preostalih nakon elektro-filtera zadržava se u apsorberu. Prečišćen dimni gas se kroz vlažni dimnjak ispušta u atmosferu. U reakcionom rezervoaru na dnu absorbera dobijaju se kristali gipsa kao proizvod hemijske reakcije krečnjaka i sumpornih oksida iz dimnog gasa.
Postrojenje se sastoji iz dva toranjska absorbera sa suprotosmernim tokovima dimnog gasa i krečnjačke suspenzije, po jedan za svaki blok, kapaciteta 6.554.469 Nm3/h dimnog gasa. Ubrizgavanje krečnjačke suspenzije se vrši pomoću mlaznica koje su unutar absorbera postavljene u više nivoa.
Takođe se gradi i postrojenje za dopremu i mlevenje krečnjaka, odnosno pripremu krečnjačke suspenzije, kao i postrojenje za sušenje gipsa. Proizvedeni gips može da se odlaže na deponiju u obliku guste hidromešavine sa pepelom i šljakom ili u skladište gipsa za prodaju.
Ulazni parametri:
- Snaga po absorberu 650 MW
- Protok dimnog gasa na ulazu u absorber (vlažan) 6.554.469 Nm3/h
- Temperatura dimnog gasa 180°C
- Maks. sadržaj SO2 (6% O2, suv) 4984 mg/Nm3
- Sadržaj praškastih materija 50 mg/Nm3
Zahtevani izlazni parametri:
- Sadržaj SO2 (6% O2, suv) < 130 mg/Nm3
- Sadržaj praškastih materija < 20 mg/Nm3
- Emisija kapljica < 100 mg/Nm3
Војин Грковић (Универзитет у Новом Саду, Факултет техничких наука)
Abstrakt
У раду је размотрен концепт спрегуте еколошке и енергетске транзиције (СЕЕТ). Концепт подразумева коришћење фосилних горива уз услов постојања одговарајућег природног понора угљен-диоксида, што омогућава производњу електричне енергије без повећања садржаја угљен-диоксида у атмосфери. Шуме су узете као природни понор угљен-диоксида. Указано је на значај овог концепта за обезбеђење одреживог развоја неразвијених и земаља у развоју. Приказан је аналитички модел одређивања конкурентности спрегнуте еколошке и енергетске транзиције у односу на друге транзиционе трајекторије. Посматран је електроенергетски систем Србије са укупно осам хипотетичких транзиционих трајекторијa и то: ветроелектране 100% са и без система депоновања енергије, ветроелектране 80% + СЕЕТ 20% са новим електранама на лигнит и са наставком рада постојећих електрана, ветроелектране 50% + СЕЕТ 50% са ИДУ технологијом, са новим електранама на лигнит и са наставком рада постојећих електрана, као и са коришћењем 50% постојећег шумског потенцијала и, коначно, нуклеарне електране 100%. Конкурентност сваке од разматраних транзиционих трајекторија анализирана је помоћу две врсте индикатора. Прва је обухватала уложени капитал, произведену електричну енергију и емитовани угљен-диоксид, а друга различите аспекте диспечебилности електроенергетског система. Добијени резултати дефинишу место спрегнуте еколошке и енергетске транзиције у оквиру укупне енергетске транзиције земље. У раду је још указано на потребу дефинисања и реализације два пројекта. Први се односи на квантификацију капацитета шума и хидрофлоре у Србији за апсорпцију угљен-диоксида. Други се односи на испитивање и дефинисање могућности корићења старих лежишта природног гаса за депоновање угљен-диоксида.